中文 繁体中文 English Русский язык Deutsch Français Español Português Italiano بالعربية Türkçe 日本語 한국어 ภาษาไทย Tiếng Việt

Voltage Drop Calculator

This is a calculator for the estimation of the voltage drop of an electrical circuit. The "NEC data" tab calculates based on the resistance and reactance data from the National Electrical Code (NEC). The "Estimated resistance" tab calculates based on the resistance data estimated from the wire size. Click the "Other" tab to use customized resistance or impedance data, such as data from other standards or wire manufacturers.


Modify the values and click the calculate button to use
Wire material
Wire size
Material of conduit
Power factor (PF)
Wire material
Wire size
Wire impendence
or resistance
Voltage
Phase
Number of conductors
Distance (one-way)
Load current Amps

When electrical current moves through a wire, it is pushed by electrical potential (voltage) and it needs to surpass a certain level of contrary pressure caused by the wire. The voltage drop is the amount of electrical potential (voltage) loss caused by the contrary pressure of the wire. If the current is alternating, such contrary pressure is called impedance. Impedance is a vector, or two-dimensional quantity, consisting of resistance and reactance (reaction of a built-up electric field to a change of current). If the current is direct, the contrary pressure is called resistance.

Excessive voltage drop in a circuit can cause lights to flicker or burn dimly, heaters to heat poorly, and motors to run hotter than normal and burn out. It is recommended that the voltage drop should be less than 5% under a fully loaded condition. This can be achieved by selecting the right wire, and by taking care in the use of extension cords and similar devices.

There are four major causes of voltage drop:

The first is the choice of material used for the wire. Silver, copper, gold, and aluminum are among the metals with the best electrical conductivity. Copper and aluminum are the most common materials used for wires due to their relatively low price compared with silver and gold. Copper is a better conductor than aluminum and will have less voltage drop than aluminum for a given length and wire size.

Wire size is another important factor in determining voltage drop. Larger wire sizes (those with a greater diameter) will have less voltage drop than smaller wire sizes of the same length. In American wire gauge, every 6-gauge decrease doubles the wire diameter, and every 3-gauge decrease doubles the wire cross sectional area. In the Metric Gauge scale, the gauge is 10 times the diameter in millimeters, so a 50 gauge metric wire would be 5 mm in diameter.

Still another critical factor in voltage drop is wire length. Shorter wires will have less voltage drop than longer wires for the same wire size. Voltage drop becomes important when the length of a run of wire or cable becomes very long. Usually this is not a problem in circuits within a house, but may become an issue when running wire to an outbuilding, well pump, etc.

Finally, the amount of current being carried can affect voltage drop levels; an increase in current through a wire results in an increased voltage drop. Current carrying capacity is often referred to as ampacity, which is the maximum number of electrons that can be pushed at one time – the word ampacity is short for ampere capacity.

The ampacity of a wire depends on a number of factors. The basic material from which the wire is made is, of course, an important limiting factor. If alternating current is being sent through the wire, the speed of alternation can affect ampacity. The temperature in which the wire is used can also affect ampacity.

Cables are often used in bundles, and when they are brought together, the total heat which they generate has an effect on ampacity and voltage drop. There are strict rules about bundling cables which must be followed for this reason.

Cable selection is guided by two main principles. First, the cable should be able to carry the current load imposed on it without overheating. It should be able to do this in the most extreme conditions of temperature it will encounter during its working life. Second, it should offer sufficiently sound earthing to (i) limit the voltage to which people are exposed to a safe level and (ii) allow the fault current to trip the fuse in a short time.

Voltage drop calculation

Ohm's Law is a very basic law for calculating voltage drop:

Vdrop = I·R

where:

I: the current through the wire, measured in amperes
R: the resistance of the wires, measured in ohms

The resistance of the wires is often measured and given as length-specific resistance, normally in the unit of ohms per kilometer or ohms per 1000 feet. Also, the wire is round-tripped. Therefore, the formula for a single-phase or direct current circuit becomes:

Vdrop = 2·I·R·L

The formula for a three-phase circuit becomes:

Vdrop = √3·I·R·L

where:

I: the current through the wire
R: the length-specific resistance of the wires
L: the one-way length

Typical AWG wire sizes

American Wire Gauge (AWG) is a wire gauge system used predominantly in North America for the diameters of round, solid, non-ferrous, electrically conducting wire. The following is a list of typical AWG wires and their sizes:

AWG Diameter Turns of wire Area Copper resistance
inch mm per inch per cm kcmil mm2 Ω/km Ω/1000ft
0000 (4/0) 0.4600 11.684 2.17 0.856 212 107 0.1608 0.04901
000 (3/0) 0.4096 10.404 2.44 0.961 168 85.0 0.2028 0.06180
00 (2/0) 0.3648 9.266 2.74 1.08 133 67.4 0.2557 0.07793
0 (1/0) 0.3249 8.252 3.08 1.21 106 53.5 0.3224 0.09827
1 0.2893 7.348 3.46 1.36 83.7 42.4 0.4066 0.1239
2 0.2576 6.544 3.88 1.53 66.4 33.6 0.5127 0.1563
3 0.2294 5.827 4.36 1.72 52.6 26.7 0.6465 0.1970
4 0.2043 5.189 4.89 1.93 41.7 21.2 0.8152 0.2485
5 0.1819 4.621 5.50 2.16 33.1 16.8 1.028 0.3133
6 0.1620 4.115 6.17 2.43 26.3 13.3 1.296 0.3951
7 0.1443 3.665 6.93 2.73 20.8 10.5 1.634 0.4982
8 0.1285 3.264 7.78 3.06 16.5 8.37 2.061 0.6282
9 0.1144 2.906 8.74 3.44 13.1 6.63 2.599 0.7921
10 0.1019 2.588 9.81 3.86 10.4 5.26 3.277 0.9989
11 0.0907 2.305 11.0 4.34 8.23 4.17 4.132 1.260
12 0.0808 2.053 12.4 4.87 6.53 3.31 5.211 1.588
13 0.0720 1.828 13.9 5.47 5.18 2.62 6.571 2.003
14 0.0641 1.628 15.6 6.14 4.11 2.08 8.286 2.525
15 0.0571 1.450 17.5 6.90 3.26 1.65 10.45 3.184
16 0.0508 1.291 19.7 7.75 2.58 1.31 13.17 4.016
17 0.0453 1.150 22.1 8.70 2.05 1.04 16.61 5.064
18 0.0403 1.024 24.8 9.77 1.62 0.823 20.95 6.385
19 0.0359 0.912 27.9 11.0 1.29 0.653 26.42 8.051
20 0.0320 0.812 31.3 12.3 1.02 0.518 33.31 10.15
21 0.0285 0.723 35.1 13.8 0.810 0.410 42.00 12.80
22 0.0253 0.644 39.5 15.5 0.642 0.326 52.96 16.14
23 0.0226 0.573 44.3 17.4 0.509 0.258 66.79 20.36
24 0.0201 0.511 49.7 19.6 0.404 0.205 84.22 25.67
25 0.0179 0.455 55.9 22.0 0.320 0.162 106.2 32.37
26 0.0159 0.405 62.7 24.7 0.254 0.129 133.9 40.81
27 0.0142 0.361 70.4 27.7 0.202 0.102 168.9 51.47
28 0.0126 0.321 79.1 31.1 0.160 0.0810 212.9 64.90
29 0.0113 0.286 88.8 35.0 0.127 0.0642 268.5 81.84
30 0.0100 0.255 99.7 39.3 0.101 0.0509 338.6 103.2
31 0.00893 0.227 112 44.1 0.0797 0.0404 426.9 130.1
32 0.00795 0.202 126 49.5 0.0632 0.0320 538.3 164.1
33 0.00708 0.180 141 55.6 0.0501 0.0254 678.8 206.9
34 0.00630 0.160 159 62.4 0.0398 0.0201 856.0 260.9
35 0.00561 0.143 178 70.1 0.0315 0.0160 1079 329.0
36 0.00500 0.127 200 78.7 0.0250 0.0127 1361 414.8
37 0.00445 0.113 225 88.4 0.0198 0.0100 1716 523.1
38 0.00397 0.101 252 99.3 0.0157 0.00797 2164 659.6
39 0.00353 0.0897 283 111 0.0125 0.00632 2729 831.8
40 0.00314 0.0799 318 125 0.00989 0.00501 3441 1049
Financial Fitness & Health Math Other